This paper describes the measurement strategy adopted by the LATFC - Laboratorio Alte Tensioni Forti Correnti- High Voltage and High Power Laboratory of the Istituto Nazionale di Ricerca Metrologica (INRiM) to extend the measurement capability of the Joule integral up to 10 GA2s. This is achieved by means of the application of a short-circuit current of 100 kA for 1 s. The measurement is currently under investigation and the capability has been preliminarily evaluated on the order of 3.5 %. The system needs an energy validation that will be made by comparison with a low-value, long-duration steady-state current transformer
Measuring the Impact of Heat Waves on Underground Medium Voltage Cables: Evidence From a Field Measurement Campaign / Roccato, P.E., Galliana, F., Caria, S.E., Picco, V., Mazza, A.. - (2026). (35th edition of the CPEM, « Conference on Precision Electromagnetic Measurements MADRID 6th to the 11th of September 2026) [10.1109/CPEM68396.2026.11756437].
Measuring the Impact of Heat Waves on Underground Medium Voltage Cables: Evidence From a Field Measurement Campaign
P. E. Roccato
Conceptualization
;F. GallianaWriting – Original Draft Preparation
;S. E. CariaMethodology
;
2026
Abstract
This paper describes the measurement strategy adopted by the LATFC - Laboratorio Alte Tensioni Forti Correnti- High Voltage and High Power Laboratory of the Istituto Nazionale di Ricerca Metrologica (INRiM) to extend the measurement capability of the Joule integral up to 10 GA2s. This is achieved by means of the application of a short-circuit current of 100 kA for 1 s. The measurement is currently under investigation and the capability has been preliminarily evaluated on the order of 3.5 %. The system needs an energy validation that will be made by comparison with a low-value, long-duration steady-state current transformerI documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.